ABB Relion 670 Series Technical Reference Manual page 648

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 12
Control
642
CLOSECMD
CBClosed
52a
RI
ANSI05000787 V1 EN
Figure 320:
Automatic proceeding of shot 2 to 5
Initiation of reclosing from CB open information
If a user wants to apply initiation of auto-reclosing from CB open position instead of
from protection trip signals, the function offers such a possibility. This starting mode is
selected by a setting parameter StartByCBOpen = Enabled. One needs then to block
reclosing at all manual trip operations. Typically, one also set CBAuxContType =
NormClosed and connect a CB auxiliary contact of type NC (normally closed, 52b) to
inputs 52a and RI. When the signal changes from CB closed to CB open an auto-
reclosing start pulse of limited length is generated and latched in the function, subject
to the usual checks. Then the reclosing sequence continues as usual. One needs to
connect signals from manual tripping and other functions, which shall prevent
reclosing, to the input INHIBIT.
0-tAutoContWait
S
Q
AND
R
AND
OR
1MRK505222-UUS C
0
AND
initiate
OR
en05000787_ansi.vsd
Technical reference manual