Figure 304:
Simplified logic diagram for main logic of Fuse failure function
Delta current and delta voltage detection
A simplified diagram for the functionality is found in figure 305. The calculation of the
change is based on vector change which means that it detects both amplitude and phase
angle changes. The calculated delta quantities are compared with their respective set
values DI< and DU> and the algorithm, detects a fuse failure if a sufficient change in
voltage without a sufficient change in current is detected in each phase separately. The
following quantities are calculated in all three phases:
The change in voltage DU
The change in current DI
The internal FuseFailDetDUDI signal is activated if the following conditions are
fulfilled for a phase:
The magnitude of the phase-ground voltage has been above UPh> for more than
1.5 cycle
The magnitude of DU is higher than the corresponding setting DU>
The magnitude of DI is below the setting DI>
and at least one of the following conditions are fulfilled:
The magnitude of the phase current in the same phase is higher than the setting IPh>
The circuit breaker is closed (CBCLOSED = True)
The first criterion means that detection of failure in one phase together with high
current for the same phase will set the output. The measured phase current is used to
reduce the risk of false fuse failure detection. If the current on the protected line is low,
a voltage drop in the system (not caused by fuse failure) is not by certain followed by
current change and a false fuse failure might occur
The second criterion requires that the delta condition shall be fulfilled in any phase at
the same time as circuit breaker is closed. Opening circuit breaker at one end and
energizing the line from other end onto a fault could lead to wrong start of the fuse
failure function at the end with the open breaker. If this is considering to be an
important disadvantage, connect the CBCLOSED input to FALSE. In this way only the
first criterion can activate the delta function.