ABB Relion 670 Series Technical Reference Manual page 467

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
7.8.5
Table 221:
CCRBRF (50BF) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
FunctionMode
Current
Contact
Current&Contact
BuTripMode
2 out of 4
1 out of 3
1 out of 4
RetripMode
Retrip Off
CB Pos Check
No CBPos Check
Pickup_PH
5 - 200
Pickup_N
2 - 200
t1
0.000 - 60.000
t2
0.000 - 60.000
t2MPh
0.000 - 60.000
tPulse
0.000 - 60.000
Table 222:
CCRBRF (50BF) Group settings (advanced)
Name
Values (Range)
Pickup_BlkCont
5 - 200
t3
0.000 - 60.000
tCBAlarm
0.000 - 60.000
7.8.6
Technical reference manual
Setting parameters
Unit
Step
-
-
A
1
-
-
-
-
-
-
%IB
1
%IB
1
s
0.001
s
0.001
s
0.001
s
0.001
Unit
Step
%IB
1
s
0.001
s
0.001
Technical data
Table 223:
CCRBRF (50BF) technical data
Function
Operate phase current
Reset ratio, phase current
Operate residual current
Table continues on next page
Default
Disabled
3000
Current
1 out of 3
Retrip Off
10
10
0.000
0.150
0.150
0.200
Default
20
0.030
5.000
Range or value
lBase
(5-200)% of
> 95%
lBase
(2-200)% of
Current protection
Description
Disable/Enable Operation
Base current
Detection principle for back-up trip
Back-up trip mode
Operation mode of re-trip logic
Phase current pickup in % of IBase
Operate residual current level in % of IBase
Time delay of re-trip
Time delay of back-up trip
Time delay of back-up trip at multi-phase
pickup
Trip pulse duration
Description
Current for blocking of CB contact operation
in % of IBase
Additional time delay to 27P2TDLY for a
second back-up trip
Time delay for CB faulty signal
Accuracy
± 1.0% of I
at I £ I
n
± 1.0% of I at I > I
-
± 1.0% of I
at I £ I
n
± 1.0% of I at I > I
Section 7
n
n
n
n
461