ABB Relion 670 Series Technical Reference Manual page 401

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Name
Values (Range)
tTRCrv3
0.005 - 100.000
tCRCrv3
0.1 - 10.0
HarmRestrain3
Disabled
Enabled
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
tReset4
0.000 - 60.000
tPCrv4
0.005 - 3.000
tACrv4
0.005 - 200.000
tBCrv4
0.00 - 20.00
tCCrv4
0.1 - 10.0
tPRCrv4
0.005 - 3.000
tTRCrv4
0.005 - 100.000
tCRCrv4
0.1 - 10.0
HarmRestrain4
Disabled
Enabled
Table 193:
OC4PTOC (51_67) Non group settings (basic)
Name
Values (Range)
MeasType
DFT
RMS
Technical reference manual
Unit
Step
Default
-
0.001
13.500
-
0.1
1.0
-
-
Disabled
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
-
-
Disabled
Unit
Step
Default
-
-
DFT
Current protection
Description
Parameter TR for customer programmable
curve for step 3
Parameter CR for customer programmable
curve for step 3
Enable block of step3 from harmonic restrain
Selection of reset curve type for step 4
Reset time delay used in IEC Definite Time
curve step 4
Parameter P for customer programmable
curve for step 4
Parameter A for customer programmable
curve for step 4
Parameter B for customer programmable
curve for step 4
Parameter C for customer programmable
curve for step 4
Parameter PR for customer programmable
curve for step 4
Parameter TR for customer programmable
curve for step 4
Parameter CR for customer programmable
curve for step 4
Enable block of step 4 from harmonic restrain
Description
Selection between DFT and RMS
measurement
Section 7
395