ABB Relion 670 Series Technical Reference Manual page 889

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
14.5
14.5.1
14.5.2
Technical reference manual
Boolean 16 to Integer conversion B16I
Function description
Boolean 16 to integer conversion
Introduction
Boolean 16 to integer conversion function (B16I) is used to transform a set of 16
binary (logical) signals into an integer.
Operation principle
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up
to 16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value
according to the table below from 0 to 32768. This follows the general formula: INx =
x-1
2
where 1≤x≤16. The sum of all the values on the activated INx will be available on
the output OUT as a sum of the values of all the inputs INx that are activated. OUT is
an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it corresponds
to that integer 65535 is available on the output OUT. B16I function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will
freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block B16I
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
Table continues on next page
IEC 61850
IEC 60617
identification
identification
B16I
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
Section 14
Logic
ANSI/IEEE C37.2
device number
-
-
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0