Section 12
Control
12.3.8.3
12.3.8.4
680
Function block
SXSWI
BLOCK
XPOS
LR_SWI
EXE_OP
OPEN
EXE_CL
CLOSE
SUBSTED
BL_OPEN
OP_BLKD
BL_CLOSE
CL_BLKD
BL_UPD
UPD_BLKD
POSOPEN
POSITION
POSCLOSE
OPENPOS
RS_CNT
CLOSEPOS
XIN
CNT_VAL
L_CAUSE
IEC05000339-2-en.vsd
IEC05000339 V2 EN
Figure 346:
SXSWI function block
Input and output signals
Table 341:
SXSWI Input signals
Name
Type
BLOCK
BOOLEAN
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
RS_CNT
BOOLEAN
XIN
BOOLEAN
Table 342:
SXSWI Output signals
Name
Type
XPOS
GROUP SIGNAL
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
SUBSTED
BOOLEAN
OP_BLKD
BOOLEAN
Table continues on next page
Default
Description
0
Block of function
0
Local/Remote switch indication from switchyard
0
Pulsed signal used to immediately open the switch
0
Pulsed signal used to immediately close the switch
0
Signal to block the open command
0
Signal to block the close command
0
Steady signal for block of the position updating
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Resets the operation counter
0
Execution information from CSWI
Description
Group signal for XSWI output
Executes the command for open direction
Executes the command for close direction
Indication that the position is substituted
Indication that the function is blocked for open
commands
1MRK505222-UUS C