ABB Relion 670 Series Technical Reference Manual page 813

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
13.3.5
Table 430:
ZCRWPSCH (85) Group settings (basic)
Name
Values (Range)
CurrRev
Disabled
Enabled
tPickUpRev
0.000 - 60.000
tDelayRev
0.000 - 60.000
WEI
Disabled
Echo
Echo & Trip
tPickUpWEI
0.000 - 60.000
VBase
0.05 - 2000.00
PU27PP
10 - 90
PU27PN
10 - 90
Technical reference manual
Name
Type
IREV
BOOLEAN
WEIBLK1
BOOLEAN
WEIBLK2
BOOLEAN
LOVBZ
BOOLEAN
CBOPEN
BOOLEAN
CRL
BOOLEAN
Table 429:
ZCRWPSCH (85) Output signals
Name
Type
IRVL
BOOLEAN
TRWEI
BOOLEAN
TRWEI_A
BOOLEAN
TRWEI_B
BOOLEAN
TRWEI_C
BOOLEAN
ECHO
BOOLEAN
Setting parameters
Unit
Step
-
-
s
0.001
s
0.001
-
-
s
0.001
kV
0.05
%VB
1
%VB
1
Scheme communication
Default
Description
0
A signal that indicates a reverse fault has been
detected and activates current reverasl logic
0
Block of WEI logic
0
Block of WEI logic due to operation of other
protections that would effect a pilot trip or the detection
of reverse faults that will be tripped by an external device
0
Block of trip from WEI logic through the loss of voltage
(fuse-failure) function
0
Block of trip from WEI logic by an open breaker
0
POTT or Unblock carrier receive for WEI logic
Description
Operation of current reversal logic
Trip of WEI logic
Trip of WEI logic in phase A
Trip of WEI logic in phase B
Trip of WEI logic in phase C
A signal that indicates channel start (CS) by WEI logic
Default
Description
Disabled
Operating mode of Current Reversal Logic
0.020
Pickup time for current reversal logic
0.060
Time Delay to prevent Carrier send and local
trip
Disabled
Operating mode of WEI logic
0.010
Coordination time for the WEI logic
400.00
Base setting for voltage level
70
Phase to Phase voltage for detection of fault
condition
70
Phase to Neutral voltage for detection of fault
condition
Section 13
807