Section 12
Control
12.4.9.1
726
Introduction
The interlocking for a double busbar double circuit breaker bay including DB_BUS_A
(3), DB_BUS_B (3) and DB_LINE (3) functions are used for a line connected to a
double busbar arrangement according to figure 369.
189
189G
DB_BUS_A
152
6189
989
989G
ANSI04000518 V1 EN
Figure 369:
Switchyard layout double circuit breaker
Three types of interlocking modules per double circuit breaker bay are defined.
DB_LINE (3) is the connection from the line to the circuit breaker parts that are
connected to the busbars. DB_BUS_A (3) and DB_BUS_B (3) are the connections
from the line to the busbars.
289
252
289G
6289
1MRK505222-UUS C
WA1 (A)
WA2 (B)
489G
DB_BUS_B
589G
389G
DB_LINE
en04000518_ansi.vsd
Technical reference manual