Technical reference manual
If the load compensated algorithms according to the above do not give a reliable
solution, a less accurate, non-compensated impedance model is used to calculate the
relative distance to the fault.
The non-compensated impedance model
In the non-compensated impedance model, I
current:
= ×
×
+
×
V
p Z
I
R I
A
1L
A
F
A
EQUATION1603 V1 EN
Where:
I
is according to table 579.
A
The accuracy of the distance-to-fault calculation, using the non-compensated
impedance model, is influenced by the pre-fault load current. So, this method is only
used if the load compensated models do not function.
IEC 60870-5-103
The communication protocol IEC 60870-5-103 may be used to poll fault location
information from the IED to a master (that is station HSI). There are two outputs that
must be connected to appropriate inputs on the function block I103StatFltDis,
FLTDISTX gives distance to fault (reactance, according the standard) and
CALCMADE gives a pulse (100 ms) when a result is obtainable on FLTDISTX output.
Function block
LMBRFLO
PHSEL_A*
FLTDISTX
PHSEL_B*
CALCMADE
PHSEL_C*
BCD_80
CALCDIST*
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1
ANSI05000679-2-en.vsd
ANSI05000679 V2 EN
Figure 470:
FLO function block
line current is used instead of I
A
Section 15
Monitoring
fault
FA
(Equation 194)
945