Technical reference manual
released, and in 2 out of 2 mode both the CRs should be high to release trip signal. If
any one of the channel error signals is high in 2 out of 2 mode, then logic automatically
switches to 1 out of 2 mode after a time delay of 200 ms. After switching to 1/2 mode
under channel error condition and if channel error gets cleared the mode will switch
back only after a time delay of 200 ms.
If the input channel error signal is high then the respective carrier receive signal will be
blocked.
The complete function can be blocked by setting the BLOCK input high.
Function block
LCCRPTRC (94)
BLOCK
TRIP
LOCTR
TR_A
LOCTR_A
TR_B
LOCTR_B
TR_C
LOCTR_C
CHERR1
CHERR2
CR!
CR2
ANSI09000766-1-en.vsd
ANSI09000766 V1 EN
Figure 420:
LCCRPTRC (94) function block
Input and output signals
Table 463:
LCCRPTRC (94) Input signals
Name
Type
BLOCK
BOOLEAN
LOCTR
BOOLEAN
LOCTR_A
BOOLEAN
LOCTR_B
BOOLEAN
LOCTR_C
BOOLEAN
CHERR1
BOOLEAN
CHERR2
BOOLEAN
CR!
BOOLEAN
CR2
BOOLEAN
Scheme communication
Default
Description
0
Block of function
0
Local common trip signal coming from DTT
0
Local trip signal for phase A coming from DTT
0
Local trip signal for phase B coming from DTT
0
Local trip signal for phase C coming from DTT
0
Channel error indication flag for carrier receive 1
0
Channel error indication flag for carrier receive 2
0
Carrier receive 1
0
Carrier receive 2
Section 13