ABB Relion 670 Series Technical Reference Manual page 847

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
13.8.4.3
13.8.4.4
13.8.4.5
Table 460:
SCCVPTOC (51) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
IPickup
0 - 100
tHold
0.000 - 60.000
Technical reference manual
If the above criteria becomes true for a time of tDelay, then respective RI output is
activated provided the BLOCK input is false, and the respective TRIP outputs is
activated for the time of tHold provided the BLKTR and BLOCK input is false.
Function block
SCCVPTOC (51)
I3P*
TRIP
BLOCK
RI
BLKTR
ANSI09000765-1-en.vsd
ANSI09000765 V1 EN
Figure 419:
SCCVPTOC (51) function block
Input and output signals
Table 458:
SCCVPTOC (51) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
Table 459:
SCCVPTOC (51) Output signals
Name
Type
TRIP
BOOLEAN
RI
BOOLEAN
Setting parameters
Unit
Step
-
-
A
1
%IB
1
s
0.001
Scheme communication
Default
Description
-
Three phase to phase current samples group
0
Block of function
0
Block trip signals
Description
Common trip signal
Common start signal
Default
Description
Disabled
Operation Off/On
3000
Base setting for current in A
20
Fixed threshold setting in % of IBase
0.500
Hold time for operate signals
Section 13