Section 6
Impedance protection
Name
Values (Range)
IphPickup
1 - 100
UVPickup
1 - 100
tDuration
0.000 - 60.000
tSOTF
0.000 - 60.000
tDLD
0.000 - 60.000
6.14.6
6.15
6.15.1
372
Unit
Step
%IB
1
%VB
1
s
0.001
s
0.001
s
0.001
Technical data
Table 178:
ZCVPSOF technical data
Parameter
Operate voltage, detection of dead line
Operate current, detection of dead line
Delay following dead line detection input before
Automatic switch into fault logic function is
automatically enabled
Time period after circuit breaker closure in which
Automatic switch into fault logic function is active
Phase preference logic PPLPHIZ
Function description
Phase preference logic
Introduction
Phase preference logic function PPLPHIZ is intended to be used in isolated or high
impedance grounded networks where there is a requirement to trip only one of the
faulty lines at cross-country fault.
Phase preference logic inhibits tripping for single phase-to-ground faults in isolated
and high impedance grounded networks, where such faults are not to be cleared by
distance protection. For cross-country faults, the logic selects either the leading or the
lagging phase-ground loop for measurement and initiates tripping of the preferred fault
Default
Description
20
Current level for detection of dead line in % of
IBase
70
Voltage level for detection of dead line in % of
VBase
0.020
Time delay for VI detection (s)
1.000
Drop off delay time of switch onto fault function
0.200
Delay time for activation of dead line detection
Range or value
(1–100)% of
VBase
(1–100)% of
IBase
(0.000–60.000) s
(0.000–60.000) s
IEC 61850
IEC 60617
identification
identification
PPLPHIZ
1MRK505222-UUS C
Accuracy
± 0.5% of V
n
± 1.0% of I
n
± 0.5% ± 10 ms
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
-
-
Technical reference manual