Technical Data - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
Table 101:
ZDRDIR (21D) Group settings (basic)
Name
Values (Range)
IBase
1 - 99999
VBase
0.05 - 2000.00
IMinPUPP
5 - 30
IMinPUPG
5 - 30
AngNegRes
90 - 175
AngDir
5 - 45
6.1.7
194
Unit
Step
A
1
kV
0.05
%IB
1
%IB
1
Deg
1
Deg
1

Technical data

Table 102:
ZMQPDIS (21) Technical data
Function
Number of zones
Minimum operate residual
current, zone 1
Minimum operate current, phase-
to-phase and phase-to-ground
Positive sequence reactance
Positive sequence resistance
Zero sequence reactance
Zero sequence resistance
Fault resistance, phase-to-
ground
Fault resistance, phase-to-phase
Dynamic overreach
Impedance zone timers
Operate time
Reset ratio
Reset time
Default
Description
3000
Base setting for current level
400.00
Base setting for voltage level
10
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
5
Minimum pickup phase current for Phase-to-
ground loops
115
Angle of blinder in second quadrant for
forward direction
15
Angle of blinder in fourth quadrant for forward
direction
Range or value
Accuracy
Max 5 with selectable
-
direction
(5-1000)% of IBase
-
(10-1000)% of IBase
-
(0.10-3000.00) Ω/
± 2.0% static accuracy
phase
± 2.0 degrees static angular accuracy
Conditions:
(0.01-1000.00) Ω/
Voltage range: (0.1-1.1) x V
phase
Current range: (0.5-30) x I
(0.10-9000.00) Ω/
Angle: at 0 degrees and 85 degrees
phase
(0.01-3000.00) Ω/
phase
(0.10-9000.00) Ω/loop
(0.10-3000.00) Ω/loop
<5% at 85 degrees
-
measured with CVT's
and 0.5<SIR<30
(0.000-60.000) s
± 0.5% ± 10 ms
24 ms typically
-
105% typically
-
30 ms typically
-
1MRK505222-UUS C
n
n
Technical reference manual