ABB Relion 670 Series Technical Reference Manual page 163

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Name
Values (Range)
RatVoltW1TraB
1.0 - 9999.9
RatVoltW2TraB
1.0 - 9999.9
ClockNumTransB
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
ZerSeqPassTraB
No
Yes
Table 79:
LT6CPDIF (87LT) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IdMin
0.20 - 2.00
IdMinHigh
0.20 - 10.00
tIdMinHigh
0.000 - 60.000
IdUnre
1.00 - 50.00
NegSeqDiffEn
Disabled
Enabled
NegSeqROA
30.0 - 120.0
IMinNegSeq
0.01 - 0.20
CrossBlockEn
No
Yes
I2/I1Ratio
5.0 - 100.0
I5/I1Ratio
5.0 - 100.0
ChargCurEnable
Disabled
Enabled
AddDelay
Disabled
Enabled
Table continues on next page
Technical reference manual
Unit
Step
Default
kV
0.1
130.0
kV
0.1
130.0
-
-
0 [0 deg]
-
-
No
Unit
Step
Default
-
-
Disabled
IB
0.01
0.30
IB
0.01
0.80
s
0.001
1.000
IB
0.01
10.00
-
-
Enabled
Deg
1.0
60.0
IB
0.01
0.04
-
-
No
%
1.0
10.0
%
1.0
25.0
-
-
Disabled
-
-
Disabled
Differential protection
Description
Transformer B rated voltage (kV) on winding
1 (HV winding)
Transformer B rated voltage (kV) on winding
2 (LV winding)
Transf. B phase shift in multiples of 30 deg, 2
for 60 deg
Yes/No for capability of transf B to transform
zero seq curr
Description
Disable/Enable Operation
Oper - restr charact., section 1 sensitivity,
multiple IBase
Initial lower sensitivity, as multiple of IBase
Time interval of initial lower sensitivity, in sec
Unrestrained differential current limit, multiple
of IBase
Off/On selection for internal / external fault
discriminator
Internal/external fault discriminator Operate
Angle, degrees
Min. value of neg. seq. curr. as multiple of
IBase
Off/On selection of the cross -block logic
Max. ratio of second harmonic to fundamental
harm dif. curr. in %
Max. ratio of fifth harmonic to fundamental
harm dif. curr. in %
Off/On selection for compensation of
charging currents
On/Off selection for delayed diff. trip command
Section 5