1MRK505222-UUS C
14.1.5
Table 493:
SMPPTRC (94) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Program
3 phase
1p/3p
1p/2p/3p
tTripMin
0.000 - 60.000
tWaitForPHS
0.020 - 0.500
Table 494:
SMPPTRC (94) Group settings (advanced)
Name
Values (Range)
TripLockout
Disabled
Enabled
AutoLock
Disabled
Enabled
14.1.6
14.2
Technical reference manual
Setting parameters
Unit
Step
-
-
-
-
s
0.001
s
0.001
Unit
Step
-
-
-
-
Technical data
Table 495:
SMPPTRC (94) technical data
Function
Trip action
Minimum trip pulse length
Timers
Trip matrix logic TMAGGIO
Function description
Trip matrix logic
Default
Description
Enabled
Disable/Enable Operation
1p/3p
Three pole; single or three pole; single, two or
three pole trip
0.150
Minimum duration of trip output signal
0.050
Secures 3-pole trip when phase selection
failed
Default
Description
Disabled
If TripLockout is set to On, it will activate
output (CLLKOUT) and trip latch. If set to Off
it will activate only CLLKOUT
Disabled
If AutoLock is set to On i will activate lockout
from input (SETLKOUT) and trip, If set to Off
it will activate only from SETLKOUT
Range or value
3-ph, 1/3-ph, 1/2/3-ph
(0.000-60.000) s
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
TMAGGIO
-
Section 14
Logic
Accuracy
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
-
867