ABB Relion 670 Series Technical Reference Manual page 972

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Monitoring
Name
Values (Range)
OverTrigLe38
0 - 5000
Operation39
Disabled
Enabled
NomValue39
0.0 - 999999.9
UnderTrigOp39
Disabled
Enabled
UnderTrigLe39
0 - 200
OverTrigOp39
Disabled
Enabled
OverTrigLe39
0 - 5000
Operation40
Disabled
Enabled
NomValue40
0.0 - 999999.9
UnderTrigOp40
Disabled
Enabled
UnderTrigLe40
0 - 200
OverTrigOp40
Disabled
Enabled
OverTrigLe40
0 - 5000
Table 595:
B1RBDR Non group settings (basic)
Name
Values (Range)
Operation01
Disabled
Enabled
TrigLevel01
Trig on 0
Trig on 1
IndicationMa01
Hide
Show
SetLED01
Disabled
Enabled
Operation02
Disabled
Enabled
TrigLevel02
Trig on 0
Trig on 1
IndicationMa02
Hide
Show
SetLED02
Disabled
Enabled
Table continues on next page
966
Unit
Step
Default
%
1
200
-
-
Disabled
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
-
-
Disabled
-
0.1
0.0
-
-
Disabled
%
1
50
-
-
Disabled
%
1
200
Unit
Step
Default
-
-
Disabled
-
-
Trig on 1
-
-
Hide
-
-
Disabled
-
-
Disabled
-
-
Trig on 1
-
-
Hide
-
-
Disabled
1MRK505222-UUS C
Description
Over trigger level for analog cha 38 in % of
signal
Operation On/off
Nominal value for analog channel 39
Use under level trig for analog cha 39 (on) or
not (off)
Under trigger level for analog cha 39 in % of
signal
Use over level trig for analog cha 39 (on) or
not (off)
Over trigger level for analog cha 39 in % of
signal
Operation On/off
Nominal value for analog channel 40
Use under level trig for analog cha 40 (on) or
not (off)
Under trigger level for analog cha 40 in % of
signal
Use over level trig for analog cha 40 (on) or
not (off)
Over trigger level for analog cha 40 in % of
signal
Description
Trigger operation On/Off
Trig on positiv (1) or negative (0) slope for
binary inp 1
Indication mask for binary channel 1
Set red-LED on HMI for binary channel 1
Trigger operation On/Off
Trig on positiv (1) or negative (0) slope for
binary inp 2
Indication mask for binary channel 2
Set red-LED on HMI for binary channel 2
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670