Function Block; Input And Output Signals; Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
6.14.3
6.14.4
6.14.5
Table 177:
ZCVPSOF Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
Mode
Impedance
VILevel
VILvl&Imp
AutoInit
Disabled
Enabled
Table continues on next page
Technical reference manual

Function block

ZCVPSOF
I3P*
TRIP
V3P*
BLOCK
BC
ZACC
ANSI06000459-2-en.vsd
ANSI06000459 V2 EN
Figure 197:
ZCVPSOF function block

Input and output signals

Table 175:
ZCVPSOF Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BC
BOOLEAN
ZACC
BOOLEAN
Table 176:
ZCVPSOF Output signals
Name
Type
TRIP
BOOLEAN

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
-
-
-
-
Default
Description
-
Current DFT
-
Voltage DFT
0
Block of function
0
External enabling of SOTF
0
Distance zone to be accelerated by SOTF
Description
Trip by pilot communication scheme logic
Default
Description
Enabled
Disable/Enable Operation
3000
Base current (A)
400.00
Base voltage Ph-Ph (kV)
VILevel
Mode of operation of SOTF Function
Disabled
Automatic switch onto fault initialization
Section 6
Impedance protection
371