Table 124:
ZMMPDIS (21) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
PICKUP
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
PHPUND
BOOLEAN
Table 125:
ZMMAPDIS (21) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKZ
BOOLEAN
BLKTR
BOOLEAN
PHSEL
INTEGER
DIRCND
INTEGER
Table 126:
ZMMAPDIS (21) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
PICKUP
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
PHPUND
BOOLEAN
Description
General Trip, issued from any phase or loop
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
General Pickup, issued from any phase or loop
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Non-directional pickup, issued from any selected
phase or loop
Default
Description
-
Group signal for current input
-
Group signal for voltage input
0
Block of function
0
Blocks all output for LOV (or fuse failure) condition
0
Blocks all trip outputs
0
Faulted phase loop selection enable from phase
selector
0
External directional condition
Description
General Trip, issued from any phase or loop
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
General Pickup, issued from any phase or loop
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Non-directional pickup, issued from any selected
phase or loop