Technical reference manual
Logic block
Quantity with cycle time
fast
LogicGate
10
LogicTimer
10
LogicPulseTimer
10
LogicTimerSet
10
LogicLoopDelay
10
Trip Matrix Logic
6
Boolean 16 to Integer
4
Boolean 16 to
4
integer with Logic
Node
Integer to Boolean 16
4
Integer to Boolean
4
16 with Logic Node
Fixed signal function block FXDSIGN
Function description
Fixed signals
The Fixed signals function (FXDSIGN) generates a number of pre-set (fixed) signals
that can be used in the configuration of an IED, either for forcing the unused inputs in
other function blocks to a certain level/value, or for creating certain logic.
Principle of operation
There are eight outputs from FXDSIGN function block:
OFF is a boolean signal, fixed to OFF (boolean 0) value
ON is a boolean signal, fixed to ON (boolean 1) value
INTZERO is an integer number, fixed to integer value 0
INTONE is an integer number, fixed to integer value 1
INTALONE is an integer value FFFF (hex)
REALZERO is a floating point real number, fixed to 0.0 value
Range or value
medium
normal
10
20
-
10
20
(0.000–
90000.000) s
10
20
(0.000–
90000.000) s
10
20
(0.000–
90000.000) s
10
20
(0.000–
90000.000) s
6
-
-
4
8
-
4
8
-
4
8
-
4
8
-
IEC 61850
IEC 60617
identification
identification
FXDSIGN
-
Section 14
Logic
Accuracy
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
-
-
-
-
-
ANSI/IEEE C37.2
device number
-
881