Section 7
Current protection
7.1.3
7.1.4
380
There is an operation mode (OpModeSel) setting: 1 out of 3 or 2 out of 3. If the
parameter is set to 1 out of 3 any phase trip signal will be activated. If the parameter is
set to 2 out of 3 at least two phase signals must be activated for trip.
There is also a possibility to activate a preset change of the set operation current
(MultPU) via a binary input (MULTPU). In some applications the operation value
needs to be changed, for example due to transformer inrush currents.
PHPIOC (50) can be blocked from the binary input BLOCK.

Function block

PHPIOC (50)
I3P*
TRIP
BLOCK
TR_A
MULTPU
TR_B
TR_C
ANSI04000391-2-en.vsd
ANSI04000391 V2 EN
Figure 200:
PHPIOC (50) function block

Input and output signals

Table 184:
PHPIOC (50) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
MULTPU
BOOLEAN
Table 185:
PHPIOC (50) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
Default
Description
-
Three phase current
0
Block of function
0
Enable current pickup value multiplier
Description
Trip signal from any phase
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C