Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 5
Differential protection
5.1.5
Table 70:
L3CPDIF (87L) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IdMin
0.20 - 2.00
IdMinHigh
0.20 - 10.00
tIdMinHigh
0.000 - 60.000
IdUnre
1.00 - 50.00
NegSeqDiffEn
Disabled
Enabled
NegSeqROA
30.0 - 120.0
IMinNegSeq
0.01 - 0.20
CrossBlockEn
No
Yes
ChargCurEnable
Disabled
Enabled
AddDelay
Disabled
Enabled
IMaxAddDelay
0.20 - 5.00
tDefTime
0.000 - 6.000
tMinInv
0.001 - 6.000
Table continues on next page
150
Table 69:
LDLPDIF (87L) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
TRLOCAL
BOOLEAN
TRLOC_A
BOOLEAN
TRLOC_B
BOOLEAN
TRLOC_C
BOOLEAN
TRREMOTE
BOOLEAN
DIFLBLKD
BOOLEAN

Setting parameters

Unit
Step
-
-
IB
0.01
IB
0.01
s
0.001
IB
0.01
-
-
Deg
1.0
IB
0.01
-
-
-
-
-
-
IB
0.01
s
0.001
s
0.001
Description
General trip from differential protection system
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
Trip from local differential function
Trip from local differential function in phase A
Trip from local differential function in phase B
Trip from local differential function in phase C
Trip from remote differential function
Local line differential function blocked
Default
Description
Disabled
Disable/Enable Operation
0.30
Oper - restr charact., section 1 sensitivity,
multiple IBase
0.80
Initial lower sensitivity, as multiple of IBase
1.000
Time interval of initial lower sensitivity, in sec
10.00
Unrestrained differential current limit, multiple
of IBase
Enabled
Off/On selection for internal / external fault
discriminator
60.0
Internal/external fault discriminator Operate
Angle, degrees
0.04
Min. value of neg. seq. curr. as multiple of
IBase
No
Off/On selection of the cross -block logic
Disabled
Off/On selection for compensation of
charging currents
Disabled
Off/On selection for delayed diff. trip command
1.00
Below limit, extra delay can be applied,
multiple of IBase
0.000
Definite time additional delay in seconds
0.010
Inverse Delay Minimum Time. In seconds
1MRK505222-UUS C
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents