ZMRAPDIS (21)
I3P*
TRIP
V3P*
TR_A
BLOCK
TR_B
BLKZ
TR_C
BLKTR
BFI
PHSEL
PU_A
DIRCND
BFI_B
PU_C
PHPUND
ANSI08000290_1_en.vsd
ANSI08000290 V1 EN
Figure 168:
ZMRAPDIS (21) function block
ZDRDIR
I3P*
STDIRCND
U3P*
IEC09000639-1-en.vsd
IEC09000639 V1 EN

Input and output signals

Table 146:
ZMRPDIS (21) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKZ
BOOLEAN
BLKTR
BOOLEAN
PHSEL
INTEGER
DIRCND
INTEGER
Table 147:
ZMRPDIS (21) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
RI
BOOLEAN
BFI_A
BOOLEAN
Table continues on next page
Impedance protection
Default
Description
-
Group signal for current input
-
Group signal for voltage input
0
Block of function
0
Blocks all output for LOV (or fuse failure) condition
0
Blocks all trip outputs
0
Faulted phase loop selection enable from phase
selector
0
External directional condition
Description
General Trip, issued from any phase or loop
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
General Pickup, issued from any phase or loop
Pickup signal from phase A
Section 6