Technical reference manual
Function block
ZC1PPSCH (85)
BLOCK
TRIP
BLKTR
TR_A
BLKTRL1
TR_B
BLKTRL2
TR_C
BLKTRL3
CS_A
CACCL1
CS_B
CACCL2
CS_C
CACCL3
CSMPH
CSURL1
CRL_A
CSURL2
CRL_B
CSURL3
CRL_C
CSORL1
CSORL2
CSORL3
CSBLKL1
CSBLKL2
CSBLKL3
BLKCSL1
BLKCSL2
BLKCSL3
CRL1
CRL2
CRL3
CRMPH
ANSI06000427-2-en.vsd
ANSI06000427 V2 EN
Figure 394:
ZC1PPSCH (85) function block
Input and output signals
Table 424:
ZC1PPSCH (85) Input signals
Name
Type
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLKTRL1
BOOLEAN
BLKTRL2
BOOLEAN
BLKTRL3
BOOLEAN
CACCL1
BOOLEAN
CACCL2
BOOLEAN
CACCL3
BOOLEAN
CSURL1
BOOLEAN
Table continues on next page
Scheme communication
Default
Description
0
Block of function
0
Common signal for block of trip output from
communication logic in all phases
0
Signal for block of trip output from communication
logic in Phase L1
0
Signal for block of trip output from communication
logic in Phase L2
0
Signal for block of trip output from communication
logic in Phase L3
0
Accelerated Distance protection zone start in Phase L1
0
Accelerated Distance protection zone signal in Phase
L2
0
Accelerated Distance protection zone signal in Phase
L3
0
Underreaching distance protection zone signal in
Phase L1
Section 13
801