ABB Relion 670 Series Technical Reference Manual page 346

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
340
IRELPG
AND
ZMA
AND
ZMB
AND
ZMC
ZMAB
AND
ZMBC3
AND
ZMCA
AND
IRELPP
ANSI00000545 V3 EN
Figure 179:
Composition on non-directional phase selection signals
Composition of the directional (forward and reverse) phase selective signals is
presented schematically in figure
as a condition for the correct phase selection in order to secure a high phase selectivity
for simultaneous and evolving faults on lines within the complex network
configurations. Internal signals DFWLn and DFWLnLm present the corresponding
directional signals for measuring loops with phases Ln and Lm. Designation FW
(figure 113) represents the forward direction as well as the designation RV (figure 112)
represents the reverse direction. All directional signals are derived within the
corresponding digital signal processor.
Figure
112
presents additionally a composition of a PHSELZ output signal, which is
created on the basis of impedance measuring conditions. This signal can be configured
to PHSEL functional input signals of the distance protection zone and this way
influence the operation of the phase-to-phase and phase-to-ground zone measuring
elements and their phase related pickup and tripping signals.
INDIR_A
INDIR_B
INDIR_3
OR
0
15 ms
0
OR
15 ms
0
OR
15 ms
OR
0
15 ms
INDIR_AB
INDIR_BC
INDIR_CA
OR
0
15 ms
112
and figure 113. The directional criteria appears
1MRK505222-UUS C
PHSEL_G
PHSEL_A
PHSEL_B
PHSEL_C
PHSEL_PP
ANSI00000545-3-en.vsd
Technical reference manual