ABB Relion 670 Series Technical Reference Manual page 680

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 12
Control
12.3.7.3
12.3.7.4
674
Function block
SXCBR
BLOCK
XPOS
LR_SWI
EXE_OP
OPEN
EXE_CL
CLOSE
SUBSTED
BL_OPEN
OP_BLKD
BL_CLOSE
CL_BLKD
BL_UPD
UPD_BLKD
POSOPEN
POSITION
POSCLOSE
OPENPOS
TR_OPEN
CLOSEPOS
TR_CLOSE
TR_POS
RS_CNT
CNT_VAL
XIN
L_CAUSE
IEC05000338-2-en.vsd
IEC05000338 V2 EN
Figure 341:
SXCBR function block
Input and output signals
Table 338:
SXCBR Input signals
Name
Type
BLOCK
BOOLEAN
LR_SWI
BOOLEAN
OPEN
BOOLEAN
CLOSE
BOOLEAN
BL_OPEN
BOOLEAN
BL_CLOSE
BOOLEAN
BL_UPD
BOOLEAN
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
TR_OPEN
BOOLEAN
TR_CLOSE
BOOLEAN
RS_CNT
BOOLEAN
XIN
BOOLEAN
Table 339:
SXCBR Output signals
Name
Type
XPOS
GROUP SIGNAL
EXE_OP
BOOLEAN
EXE_CL
BOOLEAN
Table continues on next page
Default
Description
0
Block of function
0
Local/Remote switch indication from switchyard
0
Pulsed signal used to immediately open the switch
0
Pulsed signal used to immediately close the switch
0
Signal to block the open command
0
Signal to block the close command
0
Steady signal for block of the position updating
0
Signal for open position of apparatus from I/O
0
Signal for close position of apparatus from I/O
0
Signal for open position of truck from I/O
0
Signal for close position of truck from I/O
0
Resets the operation counter
0
Execution information from CSWI
Description
Group signal for XCBR output
Executes the command for open direction
Executes the command for close direction
1MRK505222-UUS C
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents