Section 6
Impedance protection
296
will be active see figure 150. Only one sector signal is allowed to be activated at the
same time.
The sector function for condition 1 has an internal release signal which is active if the
main sequence function has classified the angle between V
following conditions must be fulfilled for activating the release signals:
|V
|>V2MinOp
2
|3I
|> 0.05 · IBase
0
|3I
|>maxIph · INRelPG
0
where:
V
and IN
2
V2MinOp
maxIph
The angle difference is phase shifted by 180 degrees if the fault is in reverse direction.
The condition 2 looks at the angle relationship between the negative sequence voltage
V
and the positive sequence voltage V
2
relationship, there is no need for shifting phases if the fault is in reverse direction. A
phase shift is introduced so that the fault sectors will have the same angle boarders as
for condition 1. If the calculated angle between V
corresponding phase for that sector will be activated. The condition 2 is released if
both the following conditions are fulfilled:
|V
|>V2MinOp
2
|V
|>V1MinOp
1
where:
|V
| and |V
|
1
2
V1MinOP and V2MinOP
are the magnitude of the negative sequence voltage and zero-
sequence current (3I
)
0
is the setting parameter for minimum operating negative sequence
voltage
is the maximum phase current
. Since this is a phase-to-phase voltage
1
2
are the magnitude of the positive and negative sequence voltages.
are the setting parameters for positive sequence and negative sequence
minimum operating voltages.
1MRK505222-UUS C
and I
as valid. The
0
0
and V
lies within one sector, the
1
Technical reference manual