Section 4
Basic IED functions
4.11.2
4.11.3
4.11.4
108
Principle of operation
The Signal matrix for mA inputs (SMMI) function, see figure 37, receives its inputs
from the real (hardware) mA inputs via the Signal Matrix Tool (SMT), and makes
them available to the rest of the configuration via its analog outputs, named AI1 to
AI6. The inputs, as well as the whole block, can be tag-named. These tags will be
represented in SMT.
The outputs on SMMI are normally connected to the IEC61850 generic
communication I/O functions (MVGGIO) function for further use of the mA signals.
Function block
SMMI
^VIN1
AI1
^VIN2
AI2
^VIN3
AI3
^VIN4
AI4
^VIN5
AI5
^VIN6
AI6
IEC05000440-2-en.vsd
IEC05000440 V2 EN
Figure 37:
SMMI function block
Input and output signals
Table 42:
SMMI Input signals
Name
Type
VIn1
REAL
VIn2
REAL
VIn3
REAL
VIn4
REAL
VIn5
REAL
VIn6
REAL
Table 43:
SMMI Output signals
Name
Type
AI1
REAL
AI2
REAL
AI3
REAL
Table continues on next page
Default
Description
0
SMT connected milliampere input
0
SMT connected milliampere input
0
SMT connected milliampere input
0
SMT connected milliampere input
0
SMT connected milliampere input
0
SMT connected milliampere input
Description
Analog milliampere input 1
Analog milliampere input 2
Analog milliampere input 3
1MRK505222-UUS C
Technical reference manual