ABB Relion 670 Series Technical Reference Manual page 617

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
11.2.3
11.2.4
Technical reference manual
Figure 307:
Simplified logic diagram for fuse failure supervision function, Main logic
Function block
SDDRFUF
I3P*
BLKZ
V3P*
BLKV
BLOCK
3PH
52A
DLD1PH
MCBOP
DLD3PH
89B
BLKTRIP
ANSI05000700-2-en.vsd
ANSI05000700 V2 EN
Figure 308:
SDDRFUF function block
Input and output signals
Table 311:
SDDRFUF Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
52a
BOOLEAN
MCBOP
BOOLEAN
89b
BOOLEAN
BLKTRIP
BOOLEAN
Table 312:
SDDRFUF Output signals
Name
Type
BLKZ
BOOLEAN
BLKV
BOOLEAN
3PH
BOOLEAN
DLD1PH
BOOLEAN
DLD3PH
BOOLEAN
Secondary system supervision
Default
Description
-
Current connection
-
Voltage connection
0
Block of function
0
Active when circuit breaker is closed
0
Active when external Miniature Circuit Breaker opens
protected voltage circuit
0
Active when line disconnect switch is open
0
Blocks operation of function when active
Description
Start of current and voltage controlled function
General pickup
Three-phase pickup
Dead line condition in at least one phase
Dead line condition in all three phases
Section 11
611

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents