ABB Relion 670 Series Technical Reference Manual page 865

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Section 14
14.1
14.1.1
14.1.2
Technical reference manual
Logic
About this chapter
This chapter describes primarily tripping and trip logic functions. The way the
functions work, their setting parameters, function blocks, input and output signals and
technical data are included for each function.
Tripping logic SMPPTRC (94)
Function description
Tripping logic
Introduction
A function block for protection tripping is provided for each circuit breaker involved in
the tripping of the fault. It provides a settable pulse prolongation to ensure a trip pulse
of sufficient length, as well as all functionality necessary for correct co-operation with
autoreclosing functions.
The trip function block also includes a settable latch functionality for evolving faults
and breaker lock-out.
Principle of operation
The duration of a trip output signal from tripping logic common 3-phase output
SMPPTRC (94) is settable (tTripMin). The pulse length should be long enough to
secure the breaker opening.
For three-pole tripping logic common 3-phase output, SMPPTRC (94) has a single
input (TRINP_3P) through which all trip output signals from the protection functions
within the IED, or from external protection functions via one or more of the IEDs
binary inputs, are routed. It has a single trip output (TRIP) for connection to one or
IEC 61850
IEC 60617
identification
identification
SMPPTRC
I->O
SYMBOL-K V1 EN
Section 14
Logic
ANSI/IEEE C37.2
device number
94