Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
6.2.5
Table 109:
ZMCPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
OperationDir
Disabled
Non-directional
Forward
Reverse
OperationPP
Disabled
Enabled
X1FwPP
0.10 - 3000.00
R1PP
0.01 - 1000.00
RFltFwdPP
0.10 - 3000.00
X1RvPP
0.10 - 3000.00
RFltRevPP
0.10 - 3000.00
Timer tPP
Disabled
Enabled
Table continues on next page
214
Table 107:
ZDSRDIR (21D) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
Table 108:
ZDSRDIR (21D) Output signals
Name
Type
PUFW
BOOLEAN
PUREV
BOOLEAN
STDIRCND
INTEGER

Setting parameters

Settings for ZMCPDIS (21) are valid for zone 1, while settings for
ZMCAPDIS (21) are valid for zone 2 - 5
Unit
Step
-
-
A
1
kV
0.05
-
-
-
-
ohm/p
0.01
ohm/p
0.01
ohm/l
0.01
ohm/p
0.01
ohm/l
0.01
-
-
Default
Description
-
Group connection for current
-
Group connection for voltage
Description
Pickup in forward direction
Pickup in reverse direction
Binary coded directional information per measuring loop
Default
Description
Enabled
Disable/Enable Operation
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
Forward
Operation mode of directionality NonDir /
Forw / Rev
Enabled
Operation mode Disable/Enable of Phase-
Phase loops
30.00
Positive sequence reactance reach, Ph-Ph,
forward
5.00
Positive seq. resistance for characteristic
angle, Ph-Ph
30.00
Fault resistance reach, Ph-Ph, forward
30.00
Positive sequence reactance reach, Ph-Ph,
reverse
30.00
Fault resistance reach, Ph-Ph, reverse
Enabled
Operation mode Disable/Enable of Zone
timer, Ph-Ph
1MRK505222-UUS C