ABB Relion 670 Series Technical Reference Manual page 499

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
The type A curve is described as:
TD
=
t
< -
Vpickup
V
<
Vpickup
ANSIEQUATION1431 V1 EN
where:
Vpickup
Set value for step 1 and step 2
<
V
Measured voltage
The type B curve is described as:
×
TD
480
=
t
æ
Vpickup < -V
×
-
ç
32
0.5
è
<
Vpickup
EQUATION1608 V1 EN
The customer programmable curve can be created as:
é
ê
×
TD A
ê
=
t
ê
æ
< -
Vpickup
V
ê
×
-
B
C
ç
è
ë
Vpickup
EQUATION1609 V1 EN
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval Vpickup< down to
Vpickup< · (1.0 – CrvSatn/100) the used voltage will be: Vpickup< · (1.0 – CrvSatn/
100). If the programmable curve is used this parameter must be calculated so that:
CrvSatn
×
-
>
B
C
0
100
EQUATION1435 V1 EN
+
0.055
2.0
ö
÷
ø
ù
ú
ú
+
D
ú
P
ö
ú
÷
ø
û
Section 8
Voltage protection
(Equation 119)
(Equation 120)
(Equation 121)
(Equation 122)
493