ABB Relion 670 Series Technical Reference Manual page 222

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
Name
Values (Range)
X1RvPP
0.10 - 3000.00
RFltRevPP
0.10 - 3000.00
Timer tPP
Disabled
Enabled
tPP
0.000 - 60.000
OperationPG
Disabled
Enabled
X1FwPG
0.10 - 3000.00
R1PG
0.01 - 1000.00
X0PG
0.10 - 9000.00
R0PG
0.01 - 3000.00
RFltFwdPG
0.10 - 9000.00
X1RvPG
0.10 - 3000.00
RFltRevPG
0.10 - 9000.00
Timer tPG
Disabled
Enabled
tPG
0.000 - 60.000
IMinPUPP
10 - 1000
IMinPUPG
10 - 1000
Table 111:
ZDSRDIR (21D) Group settings (basic)
Name
Values (Range)
OperationSC
NoSeriesComp
SeriesComp
IBase
1 - 99999
VBase
0.05 - 2000.00
IMinPUPG
5 - 30
IMinPUPP
5 - 30
AngNegRes
90 - 175
AngDir
5 - 45
Table continues on next page
216
Unit
Step
Default
ohm/p
0.01
30.00
ohm/l
0.01
30.00
-
-
Enabled
s
0.001
0.000
-
-
Enabled
ohm/p
0.01
30.00
ohm/p
0.01
5.00
ohm/p
0.01
100.00
ohm/p
0.01
47.00
ohm/l
0.01
100.00
ohm/p
0.01
30.00
ohm/l
0.01
100.00
-
-
Enabled
s
0.001
0.000
%IB
1
20
%IB
1
20
Unit
Step
Default
-
-
SeriesComp
A
1
3000
kV
0.05
400.00
%IB
1
5
%IB
1
10
Deg
1
130
Deg
1
15
1MRK505222-UUS C
Description
Positive sequence reactance reach, Ph-Ph,
reverse
Fault resistance reach, Ph-Ph, reverse
Operation mode Disable/Enable of Zone
timer, Ph-Ph
Time delay of trip, Ph-Ph
Operation mode Disable/Enable of Phase-
Ground loops
Positive sequence reactance reach, Ph-G,
forward
Positive seq. resistance for characteristic
angle, Ph-G
Zero sequence reactance reach, Ph-G
Zero seq. resistance for zone characteristic
angle, Ph-G
Fault resistance reach, Ph-G, forward
Positive sequence reactance reach, Ph-G,
reverse
Fault resistance reach, Ph-G, reverse
Operation mode Disable/ Enable of Zone
timer, Ph-G
Time delay of trip, Ph-G
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Minimum pickup phase current for Phase-to-
ground loops
Description
Special directional criteria for voltage reversal
Base setting for current level
Base setting for voltage level
Minimum pickup phase current for Phase-to-
ground loops
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Angle of blinder in second quadrant for
forward direction
Angle of blinder in fourth quadrant for forward
direction
Technical reference manual