ABB Relion 670 Series Technical Reference Manual page 934

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Monitoring
15.2
15.2.1
15.2.2
928
Table 568:
CMSQI technical data
Function
Current positive sequence, I1
Three phase settings
Current zero sequence, 3I0
Three phase settings
Current negative sequence, I2
Three phase settings
Phase angle
Table 569:
VMSQI technical data
Function
Voltage positive sequence, U1
Voltage zero sequence, 3U0
Voltage negative sequence, U2
Phase angle
Event counter CNTGGIO
Identification
Function description
Event counter
Introduction
Event counter (CNTGGIO) has six counters which are used for storing the number of
times each counter input has been activated.
Range or value
(0.1–4.0) × I
n
(0.1–1.0) × I
n
(0.1–1.0) × I
n
(0.1–4.0) × I
n
Range or value
(10 to 300) V
(10 to 300) V
(10 to 300) V
(10 to 300) V
IEC 61850
IEC 60617
identification
identification
CNTGGIO
1MRK505222-UUS C
Accuracy
± 0.2% of I
at I ≤ 0.5 × I
n
n
± 0.2% of I at I > 0.5 × I
n
± 0.2% of I
at I ≤ 0.5 × I
n
n
± 0.2% of I at I > 0.5 × I
n
± 0.2% of I
at I ≤ 0.5 × I
n
n
± 0.2% of I at I > 0.5 × I
n
± 0.5° at 0.2 × I
< I < 0.5 × I
n
± 0.2° at 0.5 × I
≤ I < 4.0 × I
n
Accuracy
± 0.3% of V at V ≤ 50 V
± 0.2% of V at V > 50 V
± 0.3% of V at V ≤ 50 V
± 0.2% of V at V > 50 V
± 0.3% of V at V ≤ 50 V
± 0.2% of V at V > 50 V
± 0.3° at V ≤ 50 V
± 0.2° at V > 50 V
ANSI/IEEE C37.2
device number
-
S00946 V1 EN
Technical reference manual
n
n