1MRK505222-UUS C
Technical reference manual
External analog
signals
Internal analog signals
ANSI10000029 V1 EN
Figure 476:
Analog input function blocks
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated according to
the cycle time of the specific function. If a function is running at lower speed than the
base sampling rate, Disturbance recorder will use the latest updated sample until a new
updated sample is available.
If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration). In
case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.
The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used). SMAI makes the
information available as a group signal output, phase outputs and calculated residual
output (AIN-output). In situations where AI4-input is used as an input signal the
corresponding information is available on the non-calculated output (AI4) on the
SMAI function block. Connect the signals to the AxRADR accordingly.
SMAI
Block
AI3P
^GRP2_A
AI1
^GRP2_B
AI2
^GRP2_C
AI3
^GRP2_N
AI4
Type
AIN
Section 15
Monitoring
A1RADR
A2RADR
INPUT1
A3RADR
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
INPUT34
INPUT35
INPUT36
...
INPUT40