Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
6.4.5
Table 120:
ZMHPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
DirMode
Disabled
Offset
Forward
Reverse
LoadEncMode
Disabled
Enabled
ReachMode
Overreach
Underreach
OpModePG
Disabled
Enabled
ZPG
0.005 - 3000.000
ZAngPG
10 - 90
KN
0.00 - 3.00
KNAng
-180 - 180
ZRevPG
0.005 - 3000.000
tPG
0.000 - 60.000
IMinPUPG
10 - 30
OpModePP
Disabled
Enabled
ZPP
0.005 - 3000.000
ZAngPP
10 - 90
ZRevPP
0.005 - 3000.000
tPP
0.000 - 60.000
IMinPUPP
10 - 30
Technical reference manual

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
-
-
-
-
-
-
-
-
ohm/p
0.001
Deg
1
-
0.01
Deg
1
ohm/p
0.001
s
0.001
%IB
1
-
-
ohm/p
0.001
Deg
1
ohm/p
0.001
s
0.001
%IB
1
Default
Description
Enabled
Operation Enable/Disable
3000
Base current
400.00
Base voltage
Forward
Direction mode
Disabled
Load encroachment mode Off/On
Overreach
Reach mode Over/Underreach
Enabled
Operation mode Disable/Enable of Phase-
Ground loops
30.000
Positive sequence impedance setting for
Phase-Ground loop
80
Angle for positive sequence line impedance
for Phase-Ground loop
0.80
Magnitud of ground return compensation
factor KN
-15
Angle for ground return compensation factor
KN
30.000
Reverse reach of the phase to ground
loop(magnitude)
0.000
Delay time for operation of phase to ground
elements
20
Minimum operation phase to ground current
Enabled
Operation mode Disable/Enable of Phase-
Phase loops
30.000
Impedance setting reach for phase to phase
elements
85
Angle for positive sequence line impedance
for Phase-Phase elements
30.000
Reverse reach of the phase to phase
loop(magnitude)
0.000
Delay time for operation of phase to phase
20
Minimum operation phase to phase current
Section 6
Impedance protection
259