ABB Relion 670 Series Technical Reference Manual page 922

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Monitoring
Name
Values (Range)
FrLowLim
0.000 - 100.000
FrLowLowLim
0.000 - 100.000
FrLimHyst
0.000 - 100.000
VGenZeroDb
1 - 100
IGenZeroDb
1 - 100
VMagComp5
-10.000 - 10.000
VMagComp30
-10.000 - 10.000
VMagComp100
-10.000 - 10.000
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
IMagComp100
-10.000 - 10.000
IAngComp5
-10.000 - 10.000
IAngComp30
-10.000 - 10.000
IAngComp100
-10.000 - 10.000
Table 554:
CMMXU Non group settings (basic)
Name
Values (Range)
IA_DbRepInt
1 - 300
Operation
Disabled
Enabled
IBase
1 - 99999
IA_Max
0.000 -
10000000000.000
IA_RepTyp
Cyclic
Dead band
Int deadband
IA_AngDbRepInt
1 - 300
IB_DbRepInt
1 - 300
IB_Max
0.000 -
10000000000.000
Table continues on next page
916
Unit
Step
Default
Hz
0.001
47.000
Hz
0.001
45.000
%
0.001
5.000
%VB
1
5
%IB
1
5
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
%
0.001
0.000
Deg
0.001
0.000
Deg
0.001
0.000
Deg
0.001
0.000
Unit
Step
Default
Type
1
10
-
-
Disabled
A
1
3000
A
0.001
1000.000
-
-
Cyclic
Type
1
10
Type
1
10
A
0.001
1000.000
1MRK505222-UUS C
Description
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range (common for
all limits)
Zero point clamping in % of VBase
Zero point clamping in % of IBase
Magnitude factor to calibrate voltage at 5% of
Vn
Magnitude factor to calibrate voltage at 30%
of Vn
Magnitude factor to calibrate voltage at 100%
of Vn
Magnitude factor to calibrate current at 5% of
In
Magnitude factor to calibrate current at 30%
of In
Magnitude factor to calibrate current at 100%
of In
Angle calibration for current at 5% of In
Angle calibration for current at 30% of In
Angle calibration for current at 100% of In
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Disbled/Enabled operation
Base setting for current level in A
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Maximum value
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents