1MRK505222-UUS C
6.5.5
Table 127:
ZMMPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
Vbase
0.05 - 2000.00
OperationDir
Disabled
Non-directional
Forward
Reverse
X1
0.50 - 3000.00
R1
0.10 - 1000.00
X0
0.50 - 9000.00
R0
0.50 - 3000.00
RFPG
1.00 - 9000.00
Timer tPG
Disabled
Enabled
tPG
0.000 - 60.000
IMinPUPG
10 - 30
IMinOpIR
5 - 30
Table 128:
ZMMAPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
Vbase
0.05 - 2000.00
OperationDir
Disabled
Non-directional
Forward
Reverse
X1
0.50 - 3000.00
R1
0.10 - 1000.00
X0
0.50 - 9000.00
R0
0.50 - 3000.00
Table continues on next page
Technical reference manual
Setting parameters
Unit
Step
-
-
A
1
kV
0.05
-
-
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/l
0.01
-
-
s
0.001
%IB
1
%IB
1
Unit
Step
-
-
A
1
kV
0.05
-
-
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
ohm/p
0.01
Default
Description
Enabled
Disable/Enable Operation
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
Forward
Operation mode of directionality NonDir /
Forw / Rev
30.00
Positive sequence reactance reach
5.00
Positive seq. resistance for zone
characteristic angle
100.00
Zero sequence reactance reach
15.00
Zero seq. resistance for zone characteristic
angle
100.00
Fault resistance reach in ohm/loop, Ph-G
Enabled
Operation mode Disable/ Enable of Zone
timer, Ph-G
0.000
Time delay of trip, Ph-G
20
Minimum pickup phase current for Phase-to-
ground loops
5
Minimum operate residual current for Phase-
Ground loops
Default
Description
Enabled
Disable/Enable Operation
3000
Base current, i.e. rated current
400.00
Base voltage, i.e. rated voltage
Forward
Operation mode of directionality NonDir /
Forw / Rev
40.00
Positive sequence reactance reach
5.00
Positive seq. resistance for zone
characteristic angle
120.00
Zero sequence reactance reach
15.00
Zero seq. resistance for zone characteristic
angle
Section 6
Impedance protection
275