Section 5
Differential protection
Name
Values (Range)
OpenCTEnable
Disabled
Enabled
tOCTAlarmDelay
0.100 - 10.000
tOCTResetDelay
0.100 - 10.000
Table 72:
L3CPDIF (87L) Non group settings (basic)
Name
Values (Range)
NoOfTerminals
2
3
Chan2IsLocal
No
Yes
IBase
50.0 - 9999.9
Table 73:
L6CPDIF (87L) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IdMin
0.20 - 2.00
IdMinHigh
0.20 - 10.00
tIdMinHigh
0.000 - 60.000
IdUnre
1.00 - 50.00
NegSeqDiffEn
Disabled
Enabled
NegSeqROA
30.0 - 120.0
IMinNegSeq
0.01 - 0.20
CrossBlockEn
No
Yes
I2/I1Ratio
5.0 - 100.0
I5/I1Ratio
5.0 - 100.0
ChargCurEnable
Disabled
Enabled
AddDelay
Disabled
Enabled
Table continues on next page
152
Unit
Step
Default
-
-
Enabled
s
0.001
1.000
s
0.001
0.250
Unit
Step
Default
-
-
2
-
-
No
A
0.1
3000.0
Unit
Step
Default
-
-
Disabled
IB
0.01
0.30
IB
0.01
0.80
s
0.001
1.000
IB
0.01
10.00
-
-
Enabled
Deg
1.0
60.0
IB
0.01
0.04
-
-
No
%
1.0
10.0
%
1.0
25.0
-
-
Disabled
-
-
Disabled
1MRK505222-UUS C
Description
Open CTEnable Off/On
Open CT: time in s to alarm after an open CT
is detected
Reset delay in s. After delay, diff. function is
activated
Description
Number of current terminals of the protected
circuit
2-nd local current connected to input channel
2, Yes/ No
Base (reference) current of the differential
protection
Description
Disable/Enable Operation
Oper - restr charact., section 1 sensitivity,
multiple IBase
Initial lower sensitivity, as multiple of IBase
Time interval of initial lower sensitivity, in sec
Unrestrained differential current limit, multiple
of IBase
Off/On selection for internal / external fault
discriminator
Internal/external fault discriminator Operate
Angle, degrees
Min. value of neg. seq. curr. as multiple of
IBase
Off/On selection of the cross -block logic
Max. ratio of second harmonic to fundamental
harm dif. curr. in %
Max. ratio of fifth harmonic to fundamental
harm dif. curr. in %
Off/On selection for compensation of
charging currents
Off/On selection for delayed diff. trip command
Technical reference manual