Section 12
Control
12.2.3
12.2.4
648
Function block
SMBRREC (79)
ON
BLOCKED
OFF
SETON
BLKON
READY
BLKOFF
ACTIVE
RESET
SUCCL
INHIBIT
UNSUCCL
RI
INPROGR
RI_HS
1PT1
TRSOTF
2PT1
SKIPHS
3PT1
ZONESTEP
3PT2
TR2P
3PT3
TR3P
3PT4
THOLHOLD
3PT5
CBREADY
PERMIT1P
52A
PREP3P
PLCLOST
CLOSECMD
SYNC
WFMASTER
WAIT
COUNT1P
RSTCOUNT
COUNT2P
MODEINT
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
ANSI06000189-2-en.vsd
ANSI06000189 V2 EN
Figure 326:
SMBRREC (79) function block
Input and output signals
Table 320:
SMBRREC (79) Input signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
BLKON
BOOLEAN
BLKOFF
BOOLEAN
RESET
BOOLEAN
INHIBIT
BOOLEAN
RI
BOOLEAN
RI_HS
BOOLEAN
TRSOTF
BOOLEAN
SKIPHS
BOOLEAN
ZONESTEP
BOOLEAN
Table continues on next page
Default
Description
0
Switches the AR On (at Operation = ExternalCtrl)
0
Switches the AR Off (at Operation = ExternalCtrl)
0
Sets the AR in blocked state
0
Releases the AR from the blocked state
0
Resets the AR to initial conditions
0
Interrupts and inhibits reclosing sequence
0
Reclosing sequence starts by a protection trip signal
0
Start High Speed reclosing without Synchronism-
Check: t13PhHS
0
Makes AR to continue to shots 2-5 at a trip from SOTF
0
Will skip the high speed shot and continue on delayed
shots
0
Coordination between local AR and down stream
devices