ChangeLock function CHNGLCK

Introduction

Change lock function (CHNGLCK) is used to block further changes to the IED
configuration and settings once the commissioning is complete. The purpose is to
block inadvertent IED configuration changes beyond a certain point in time.

Principle of operation

The Change lock function (CHNGLCK) is configured using ACT.
The function, when activated, will still allow the following changes of the IED state
that does not involve reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group
The binary input signal LOCK controlling the function is defined in ACT or SMT:
Default
Description
SettingGroup1
ActiveSettingGroup
1
Max number of setting groups 1-6
1MRK505222-UUS C
Technical reference manual