ABB Relion 670 Series Technical Reference Manual page 919

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
15.1.5
Table 552:
CVMMXN Non group settings (basic)
Name
Values (Range)
SLowLim
0.0 - 2000.0
SLowLowLim
0.0 - 2000.0
SMin
0.0 - 2000.0
SMax
0.0 - 2000.0
SRepTyp
Cyclic
Dead band
Int deadband
PMin
-2000.0 - 2000.0
PMax
-2000.0 - 2000.0
PRepTyp
Cyclic
Dead band
Int deadband
QMin
-2000.0 - 2000.0
QMax
-2000.0 - 2000.0
QRepTyp
Cyclic
Dead band
Int deadband
PFMin
-1.000 - 1.000
PFMax
-1.000 - 1.000
PFRepTyp
Cyclic
Dead band
Int deadband
VMin
0.0 - 200.0
VMax
0.0 - 200.0
VRepTyp
Cyclic
Dead band
Int deadband
IMin
0.0 - 500.0
IMax
0.0 - 500.0
IRepTyp
Cyclic
Dead band
Int deadband
FrMin
0.000 - 100.000
FrMax
0.000 - 100.000
Table continues on next page
Technical reference manual
Setting parameters
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in PCM600.
Unit
Step
%SB
0.1
%SB
0.1
%SB
0.1
%SB
0.1
-
-
%SB
0.1
%SB
0.1
-
-
%SB
0.1
%SB
0.1
-
-
-
0.001
-
0.001
-
-
%VB
0.1
%VB
0.1
-
-
%IB
0.1
%IB
0.1
-
-
Hz
0.001
Hz
0.001
Default
Description
80.0
Low limit in % of SBase
60.0
Low Low limit in % of SBase
50.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Cyclic
Reporting type
-200.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Cyclic
Reporting type
-200.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Cyclic
Reporting type
-1.000
Minimum value
1.000
Maximum value
Cyclic
Reporting type
50.0
Minimum value in % of UBase
200.0
Maximum value in % of UBase
Cyclic
Reporting type
50.0
Minimum value in % of IBase
200.0
Maximum value in % of IBase
Cyclic
Reporting type
0.000
Minimum value
70.000
Maximum value
Section 15
Monitoring
913