Figure 258:
Voltage profile not causing a reset of the PICKUP signal for step 1, and inverse time delay
Technical reference manual
ways to reset the timer, either the timer is reset instantaneously, or the timer value is
frozen during the reset time, or the timer value is linearly decreased during the reset time..
Voltage
PICKUP
PU_Overvolt1
PICKUP
TRIP
Time
Integrator
t
Instantaneous
tIReset1
TRIP
HystAbs1
t
Frozen Timer
Section 8
Voltage protection
tIReset1
Measured
Voltage
Time
Linearly
decreased
Time
ANSI05000019-3-en.vsd