1MRK505222-UUS C
13.5.5
Table 437:
ECPSCH (85) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SchemeType
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord
0.000 - 60.000
tSendMin
0.000 - 60.000
Table 438:
ECPSCH (85) Group settings (advanced)
Name
Values (Range)
Unblock
Disabled
NoRestart
Restart
tSecurity
0.000 - 60.000
13.5.6
13.6
Technical reference manual
Setting parameters
Unit
Step
-
-
-
-
s
0.001
s
0.001
Unit
Step
-
-
s
0.001
Technical data
Table 439:
ECPSCH (85) technical data
Function
Scheme type
Communication scheme
coordination time
Current reversal and weak-end infeed logic for
residual overcurrent protection ECRWPSCH (85)
Function description
Current reversal and weak-end infeed
logic for residual overcurrent protection
Scheme communication
Default
Description
Disabled
Disable/Enable Operation
Permissive UR
Scheme type, Mode of Operation
0.035
Communication scheme channel coordination
time
0.100
Minimum duration of a carrier send signal
(carrier continuation)
Default
Description
Disabled
Operation mode of unblocking logic
0.035
Security timer for loss of carrier guard detection
Range or value
Permissive Underreaching
Permissive Overreaching
Blocking
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
ECRWPSCH
Section 13
Accuracy
-
± 0.5% ± 10 ms
ANSI/IEEE C37.2
device number
-
85
817