Section 17
Station communication
17.2.4.5
17.2.5
17.2.5.1
17.2.5.2
996
Name
Type
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
IN14
BOOLEAN
IN15
BOOLEAN
IN16
BOOLEAN
Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
IEC 61850 generic communication I/O functions MVGGIO
IEC61850 generic communication I/O functions (MVGGIO) function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
Principle of operation
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range, as
output values. In the same time, it will send over IEC 61850-8-1 the value, to other
IEC 61850 clients in the substation.
Function block
MVGGIO
BLOCK
^VALUE
^IN
RANGE
IEC05000408-2-en.vsd
IEC05000408 V2 EN
Figure 487:
MVGGIO function block
Default
Description
0
Input 7 status
0
Input 8 status
0
Input 9 status
0
Input 10 status
0
Input 11 status
0
Input 12 status
0
Input 13 status
0
Input 14 status
0
Input 15 status
0
Input 16 status
1MRK505222-UUS C
Technical reference manual