ABB Relion 670 Series Technical Reference Manual page 833

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
13.7.5
Table 446:
ZC1WPSCH (85) Group settings (basic)
Name
Values (Range)
VBase
0.05 - 2000.00
OperCurrRev
Disabled
Enabled
tPickUpRev
0.000 - 60.000
tDelayRev
0.000 - 60.000
OperationWEI
Disabled
Echo
Echo & Trip
VPGPickup
10 - 90
PU27PP
10 - 90
tPickUpWEI
0.000 - 60.000
13.7.6
Technical reference manual
Name
Type
IRVOP_B
BOOLEAN
IRVOP_C
BOOLEAN
ECHO
BOOLEAN
ECHO_A
BOOLEAN
ECHO_B
BOOLEAN
ECHO_C
BOOLEAN
Setting parameters
Unit
Step
kV
0.05
-
-
s
0.001
s
0.001
-
-
%VB
1
%VB
1
s
0.001
Technical data
Table 447:
ZC1WPSCH technical data
Function
Detection pickup phase to
neutral voltage
Detection pickup phase to phase
voltage
Reset ratio
Operate time for current reversal
Delay time for current reversal
Coordination time for weak-end
infeed logic
Scheme communication
Description
Operation of current reversal logic in Phase B
Operation of current reversal logic in Phase C
Carrier Send by WEI logic
Carrier Send by WEI logic in Phase A
Carrier Send by WEI logic in Phase B
Carrier Send by WEI logic in Phase C
Default
Description
400.00
Base setting for Voltage level
Disabled
Operating mode of Current Reversal Logic
0.020
Pickup time for current reversal logic
0.060
Time Delay to prevent Carrier send and local
trip
Disabled
Operating mode of WEI logic
70
Phase to Ground voltage for detection of fault
condition
70
Phase to Phase voltage for detection of fault
condition
0.010
Coordination time for the WEI logic
Range or value
(10-90)% of VBase
(10-90)% of VBase
<105%
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
Section 13
Accuracy
± 0.5% of V
n
± 0.5% of V
n
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
827