Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
6.6.5
Table 134:
ZDMRDIR (21D) Group settings (basic)
Name
Values (Range)
IBase
1 - 99999
VBase
0.05 - 2000.00
DirEvalType
Impedance
Comparator
Imp/Comp
AngNegRes
90 - 175
AngDir
5 - 45
IMinPUPG
5 - 30
IMinPUPP
5 - 30
Table 135:
ZDARDIR Group settings (basic)
Name
Values (Range)
IBase
1 - 99999
VBase
0.05 - 2000.00
PolMode
-3U0
-V2
IPol
Dual
-3U0Comp
-V2comp
AngleRCA
-90 - 90
IPickup
1 - 200
VPolPU
1 - 100
IPolPU
5 - 100
Table 136:
ZDARDIR Group settings (advanced)
Name
Values (Range)
AngleOp
90 - 180
Kmag
0.50 - 3000.00
284

Setting parameters

Unit
Step
-
1
-
0.05
-
-
Deg
1
Deg
1
%IB
1
%IB
1
Unit
Step
A
1
kV
0.05
-
-
Deg
1
%IB
1
%VB
1
%IB
1
Unit
Step
Deg
1
ohm
0.01
Default
Description
3000
Base setting for current level
400.00
Base setting for voltage level
Comparator
Directional evaluation mode Impedance /
Comparator
115
Angle of blinder in second quadrant for
forward direction
15
Angle of blinder in fourth quadrant for forward
direction
5
Minimum pickup phase current for Phase-to-
ground loops
10
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Default
Description
3000
Base setting for current values
400.00
Base setting for voltage level in kV
-3U0
Polarization quantity for opt dir function for P-
G faults
75
Characteristic relay angle (= MTA or base
angle)
5
Minimum operation current in % of IBase
1
Minimum polarizing voltage in % of VBase
10
Minimum polarizing current in % of IBase
Default
Description
160
Operation sector angle
40.00
Boost-factor in -V0comp and -V2comp
polarization
1MRK505222-UUS C
Technical reference manual