ABB Relion 670 Series Technical Reference Manual page 436

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
7.5.5
Table 206:
NS4PTOC (46I2) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
AngleRCA
-180 - 180
polMethod
Voltage
Dual
VPolMin
1 - 100
IPolMin
2 - 100
RPol
0.50 - 1000.00
XPol
0.50 - 3000.00
I>Dir
1 - 100
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Table continues on next page
430
Table 205:
NS4PTOC (46I2) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
TRST3
BOOLEAN
TRST4
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST2
BOOLEAN
PU_ST3
BOOLEAN
PU_ST4
BOOLEAN
PUFW
BOOLEAN
PUREV
BOOLEAN
Setting parameters
Unit
Step
-
-
A
1
kV
0.05
Deg
1
-
-
%VB
1
%IB
1
ohm
0.01
ohm
0.01
%IB
1
-
-
Description
Trip
Trip signal from step 1
Trip signal from step 2
Trip signal from step 3
Trip signal from step 4
General pickup signal
Pickup signal step 1
Pickup signal step 2
Pickup signal step 3
Pickup signal step 4
Forward directional pickup signal
Reverse directional pickup signal
Default
Description
Disabled
Disable/Enable Operation
3000
Base value for current settings
400
Base value for voltage settings
65
Relay characteristic angle (RCA)
Voltage
Type of polarization
5
Minimum voltage level for polarization in % of
VBase
5
Minimum current level for polarization in % of
IBase
5.00
Real part of neg. seq. source imp. to be used
for current polarisation
40.00
Imaginary part of neg. seq. source imp. to be
used for current polarisation
10
Neg. seq. curr. I2 level for Direction release in
% of IBase
Non-directional
Directional mode of step 1 (Disabled, Nondir,
Forward, Reverse)
1MRK505222-UUS C
Technical reference manual

Advertisement