ABB Relion 670 Series Technical Reference Manual page 435

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
7.5.3
7.5.4
Technical reference manual
Function block
NS4PTOC (46I2)
I3P*
TRIP
V3P*
TRST1
I3PPOL*
TRST2
BLOCK
TRST3
BLKTR
TRST4
BLK1
PICKUP
BLK2
PU_ST1
BLK3
PU_ST2
BLK4
PU_ST3
MULTPU1
PU_ST4
MULTPU2
PUFW
MULTPU3
PUREV
MULTPU4
ANSI09000685-1-en.vsd
ANSI09000685 V1 EN
Figure 216:
NS4PTOC (4612) function block
Input and output signals
Table 204:
NS4PTOC (46I2) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
I3PPOL
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
BLK3
BOOLEAN
BLK4
BOOLEAN
MULTPU1
BOOLEAN
MULTPU2
BOOLEAN
MULTPU3
BOOLEAN
MULTPU4
BOOLEAN
Default
Description
-
Negative Sequence 3 phase current
-
Negative Sequence 3 phase voltage
-
Negative Sequence 3 phase polarisation current
0
General block
0
Block of trip
0
Block of step 1 (Pickup and trip)
0
Block of step 2 (Pickup and trip)
0
Block of step 3 (Pickup and trip)
0
Block of step 4 (Pickup and trip)
0
When activated, the pickup multiplier is in use for step1
0
When activated, the pickup multiplier is in use for step2
0
When activated, the pickup multiplier is in use for step3
0
When activated, the pickup multiplier is in use for step4