Section 2
Analog inputs
Name
Values (Range)
VTprim8
0.05 - 2000.00
VTsec9
0.001 - 999.999
VTprim9
0.05 - 2000.00
VTsec10
0.001 - 999.999
VTprim10
0.05 - 2000.00
VTsec11
0.001 - 999.999
VTprim11
0.05 - 2000.00
VTsec12
0.001 - 999.999
VTprim12
0.05 - 2000.00
Table 4:
TRM_6I Non group settings (basic)
Name
Values (Range)
CT_WyePoint1
FromObject
ToObject
CTsec1
1 - 10
CTprim1
1 - 99999
CT_WyePoint2
FromObject
ToObject
CTsec2
1 - 10
CTprim2
1 - 99999
CT_WyePoint3
FromObject
ToObject
CTsec3
1 - 10
CTprim3
1 - 99999
CT_WyePoint4
FromObject
ToObject
CTsec4
1 - 10
CTprim4
1 - 99999
CT_WyePoint5
FromObject
ToObject
CTsec5
1 - 10
CTprim5
1 - 99999
CT_WyePoint6
FromObject
ToObject
CTsec6
1 - 10
CTprim6
1 - 99999
50
Unit
Step
Default
kV
0.05
400.00
V
0.001
110.000
kV
0.05
400.00
V
0.001
110.000
kV
0.05
400.00
V
0.001
110.000
kV
0.05
400.00
V
0.001
110.000
kV
0.05
400.00
Unit
Step
Default
-
-
ToObject
A
1
1
A
1
3000
-
-
ToObject
A
1
1
A
1
3000
-
-
ToObject
A
1
1
A
1
3000
-
-
ToObject
A
1
1
A
1
3000
-
-
ToObject
A
1
1
A
1
3000
-
-
ToObject
A
1
1
A
1
3000
1MRK505222-UUS C
Description
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Description
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
Technical reference manual