Section 6
Impedance protection
6.1.3.4
180

Measuring principles

Fault loop equations use the complex values of voltage, current, and changes in the
current. Apparent impedances are calculated and compared with the set limits. The
apparent impedances at phase-to-phase faults follow equation
to phase B fault).
V
- V
A
B
=
Z
app
I
- I
A
B
EQUATION1545 V1 EN
Here V and I represent the corresponding voltage and current phasors in the respective
phase Ln (n = 1, 2, 3)
The ground return compensation applies in a conventional manner to phase-to-ground
faults (example for a phase A to ground fault) according to equation 5.
V _ A
=
Z
app
+
×
I _ A
I
KN
N
EQUATION1546 V1 EN
Where:
V_A, I_A and IN
are the phase voltage, phase current and residual current present to the IED
KN is defined as:
-
Z0 Z1
=
KN
×
3 Z1
EQUATION-2105 V1 EN
=
+
Z
0
R
0
jX
0
EQUATION2106 V1 EN
=
+
Z
1
R
1
jX
1
EQUATION2107 V1 EN
Where
R0
is setting of the resistive zero sequence reach
X0
is setting of the reactive zero sequence reach
R1
is setting of the resistive positive sequence reach
X1
is setting of the reactive positive sequence reach
1MRK505222-UUS C
4
(example for a phase A
(Equation 4)
(Equation 5)